Florida Building Code

Free Area Based on 48x48 Unit Water Penetration Ratings Based on 48x48 Unit Wind Driven Rain Ratings Based on 39x39 Unit
Product Sheet
CSI Specification
Installation Instructions
Revit Files
Model Frame Depth Blade Angle Type Blade Style SQFT Percent Velocity (fpm) Air Volume (cfm) Pressure Loss (inwg) Wind Class Effectiveness Ratio Rainfall Rate Wind Speed Core Velocity(fpm) Airflow(cfm) AMCA CRP Listing
ECD-545 5" 45 Wind-Driven Rain Drainable Chevron 7.4 46% 1250 9250 0.22 A
B
99.40%
95.30%
3 in. hr
8 in. hr
29mph
50mph
862
975
9276
10502
Air, Water, Wind PDF Doc PDF RFA
ECV-645 6" 45 Wind-Driven Rain Vertical 7.4 46% 1250 9250 0.15 A 100% 8 in. hr 50mph 965 10,390 Water, Air, Wind PDF Doc PDF RFA
EFD-437 4" 37-1/2 Drainable/FBC Option D 9.3 58% 903 8,398 0.13 - - - - - - Air, Water PDF Doc PDF RFA
EFD-637 6" 37-1/2 Drainable/FBC Option D 9.2 58% 1113 10,242 0.15 - - - - - - Air, Water PDF Doc PDF RFA
EFJ-437 4" 37-1/2 Non-Drainable J 9.1 57% 721 6547 0.07 - - - - - - Air. Water PDF Doc PDF RFA
EFJ-445 4" 45 Non-Drainable J 8 50% 689 5549 0.08 - - - - - - Air, Water PDF Doc PDF RFA
EFK-437 4" 37-1/2 Non-Drainable K 9.1 57% 721 6547 0.07 - - - - - - Air, Water PDF Doc PDF RFA
EFK-445 4" 45 Non-Drainable K 8 50% 689 5549 0.08 - - - - - - Air, Water PDF Doc PDF RFA
Click on header to sort the results